Timber Connection Calculations
This article explains how to use the timber connection calculation module of StatiCAD. The module calculates the load-carrying capacity of the connections joining timber structural members (nailed, screwed, bolted, dowelled, plated) according to ABTHYE Section 4.11 (Eurocode 5 / Johansen models). The connection works on the selected timber members in the model; the material, section and section forces are taken automatically from the selected member.
Two ways of use: (1) The connection form described in Sections 1–8: the connection is defined and calculated by hand for one or two selected beams; the report is obtained with the Report button in the form. (2) The automatic connection design in Section 9: all timber beam ends in the model are scanned, screwed connections are designed automatically, their details are drawn and a calculation report with drawings is produced. For step-by-step use see the article Worked Example: Automatic Design of Timber Connections.
1. Opening the connection calculation
- Create the model in the normal way. The connection calculation needs timber beam(s) (design type "timber").
- In the plan view (main screen) or the 3D view, select the timber beam or beams to be connected.
- Right-click the selected member and choose "Timber Connection Calculation" from the menu that opens.
The menu item appears when the right-clicked beam is timber and a total of one or two beams are selected on the active storey; it does not appear when three or more beams are selected. If the second beam is not timber, the form opens as a single member. To be able to use the section forces from the analysis result, the analysis must have been run before opening the form (if the analysis is not up to date, the force is not taken).
1.1 One member or two members?
| Selection | Meaning |
|---|---|
| Single timber beam | The main member is filled in from the selected beam; the second member (side timber or steel plate) is entered by hand in the form. Suitable for timber–steel plate connections. |
| Two timber beams | Beam-to-beam connection. The case where one beam bears on the end of the other (bearing point) is recognised automatically; the main member (bar), the side member (stem) and the real angle between them are determined automatically. |
2. Values filled automatically from the model
When the form is opened, the data of the selected member are written automatically into the input fields (they can be overwritten if desired):
| Field | Source | Description |
|---|---|---|
| ρk (characteristic density) | Timber material assigned to the member | Densities of the Main Member and (with two members) the Side Member. If it cannot be read from the material, 350 kg/m³ is written. |
| Section dimension (t1) | Beam section width | Main member thickness; with two members, the side member thickness (t2) is also filled in. |
| VEd (design shear) | Analysis result (support shear) | The largest of the left/right support shears V2 and V3 of the member; the internal unit (ton) is converted automatically to kN. If the analysis has not been run (or the model has changed since the analysis), 0 is written; enter the value by hand. |
| Connection angle (α) | Real directions of the two beams | Angle between the members; ≈ 90° for perpendicular beams. |
| Geometry (View tab) | Positions of the selected beams | The coordinate grids of the timber member and the fastener are filled with the real geometry (see Section 5). |
3. Input tab — fields
The form has four tabs: Input, View, Results, 3D. The groups on the Input tab:
| Group | Fields |
|---|---|
| Main Member (t1) | rho_k (kg/m³), t1 (mm). |
| Reference Density | rho_a (kg/m³) — the reference density used in the fastener capacity calculation. |
| Geometry (Table 4.24) | a1, a2 (successive fastener spacings), a1,cg / a2,cg (loaded/unloaded end and edge distances), alfa (deg — force-grain angle), number of Rows and Columns. |
| Screw Properties | d_thread_outer, d_thread_root (outer / root thread diameters of the screw), f_tens,k (N) — screw tensile strength. (Active depending on the connection type.) |
| Axial Embedment / Head | l_ef (effective embedment length), f_head,k (MPa), d_h (head diameter) — for axial/head calculations. |
| Load and Factors | F_ax,Ed / V_Ed (kN), k_mod (duration-moisture factor), gamma_M (material factor), n (total number of fasteners). |
| Connection Type | Selection of the connection type (see Section 4) and the "Horizontal load (shear)" option. |
The CALCULATE button for the calculation and the Report button for the output are below the tab. The window title shows the selected connection type (e.g. Timber Connection Calculation - Screwed (axial)).
4. Connection types
The type is selected from the Connection Type group on the right. When the type is changed, the whole display (3D, grids, detail drawing) and the input defaults are rebuilt.
| Type | Calculated |
|---|---|
| Nailed | Single shear; 6 Johansen failure modes (A–F), embedment strength fh,k, yield moment My,Rk, rope effect, effective number of nails neff (Table 4.21) and geometry check (Table 4.22). |
| Screwed | Axial tension (withdrawal) and shear; density ratio correction. In a bearing-point connection, the fasteners cross the interface at a 45° inclination. |
| Stapled | Two-leg staple approach and angle factor (Table 4.23). |
| Dowelled / Bolted | Bolt/dowel shear (Eq. 4.267–4.272), k90 angle factor, Table 4.25/4.26. |
| Punched Metal Plate | Anchorage and plate capacity (Eq. 4.273–4.281). |
| Split-Ring / Shear-Plate | Ring/shear-plate connector (Eq. 4.282–4.287, Table 4.27). |
| Toothed Plate | Toothed-plate connector C1–C9 / C10–C11 (Eq. 4.288–4.289, Table 4.28/4.29). |
For each type only the relevant input fields become active; the form arranges itself according to the selected type.
5. View tab — geometry and coordinate grids
The View tab holds the geometry used in the 3D/2D drawing of the connection:
- Number of timber members, Member type (Parallel / Perpendicular / Inclined), Connection angle status and Number of fasteners: the general arrangement of the connection.
- Timber member grid (x1, y1, z1, x2, y2, z2): the centre line of each timber member. When two beams are selected, it is filled automatically from the real directions of the selected beams (in mm).
- Fastener grid (x1…z2): nail/screw positions. In screw mode the fasteners are placed crosswise at ±45° at the intersection interface; the number and spacing are adjusted to fit the interface.
- Fill Example: fills the grids with an example arrangement (for trying by hand).
The grids can be edited directly; when you change them, the 3D view is updated.
6. 3D view and drawing
6.1 3D tab
- The connection is drawn in three dimensions (OpenGL); it can be rotated with the mouse. The Wireframe box switches between wireframe / solid display.
- The end of a beam bearing on the end (bearing point) is set back from the surface of the opposite member; the boxes do not interpenetrate.
- Refresh 3D button: if the 3D image comes up blank (e.g. after switching to another program and returning), it rebuilds the drawing in the window.
- When the connection type is changed, the 3D view, grids and detail drawing are refreshed automatically.
6.2 Draw — transferring the connection to a technical drawing
The Draw button transfers the six orthographic views of the connection geometry (Top/Bottom, Front/Back, Right/Left) to the drawing screen (LiteCAD); the main member, side member and fasteners are drawn as views. It is useful for detail drawings.
For Draw, the drawing screen must be open; if it is not open, the program gives a warning.
6.3 Connection detail image
In the right part of the Input tab, for a screwed connection, a scaled detail image of the connection is shown: the sections of the main member (B) and side member (S), the ±45° crossed fasteners (F1/F2) at the joint and the arrow of the design force (VEd).
7. Calculation and results
The CALCULATE button calculates the load-carrying capacity and the utilisation ratio for the selected connection type. On the Results tab are shown: the design capacity (VRd), the demand/capacity (utilisation) ratio, the governing failure mode and the geometry check (edge/spacing conditions).
For all types, the CALCULATE result is written to the Results tab and Report opens the calculation report in preview. For the screwed type, this form checks the axial (or shear, if horizontal load is selected) strength of a single screw group; for the whole of a crossed / inclined screwed beam connection, use the automatic design in Section 9. In the axial check, the strengths related to the timber (withdrawal of the threaded part, head embedment) are calculated with kmod / γM, and the steel tensile strength of the screw, independently of the load duration, with Ft,Rd = nef · ftens,k / γM2 (γM2 = 1.25).
When changing the type: the same input boxes hold different quantities depending on the type (e.g. L length for a nail, d_thread_root for a screw; f_u in MPa for a nail, f_tens,k in N for a screw). When you switch to the screwed type or leave it, these boxes return to the type's own default values; the density, thickness and load fields are kept.
8. Notes and limitations
Responsibility: The connection calculation is concerned with the load-carrying capacity of the fasteners; the results and the connection detail must be checked by the responsible engineer.
- If VEd = 0, the model has not yet been analysed; after the analysis the support shear is filled in automatically (or you can enter the value by hand).
- If ρk is blank, no timber material may have been assigned to the selected member; assign a material or enter the value by hand.
- The number and spacing of fasteners can be adjusted automatically according to the intersection interface; you can see/change the values you entered on the View tab.
9. Automatic connection design (screwed shear connections)
The program scans the ends of all timber beams in the model, finds by itself which member each end is connected to, designs the screwed connection automatically from the support shear in the analysis, draws its detail and produces the calculation report. There is no need to select members one by one and fill in a form. For step-by-step use with screenshots: Worked Example: Automatic Design of Timber Connections.
Version: Automatic connection design is available in the Ultimate and Hybrid versions. In the demo version, the calculation report, detail drawing and layout plan are limited to the first three detail types (3 connections), and the report cannot be written to a file (PDF).
9.1 Running
- Build the model and run the analysis (the design shear is taken from the analysis result).
- In the plan view, right-click (on a member or on an empty area) and choose "Automatically Design Timber Connections" from the menu. The item is visible if there is a timber beam in the project; there is no need to select a member.
- The window rescans the model every time it opens and lists the connections as designed. If you change the options, recalculate with the Scan and Design button.
If you change the model or re-run the analysis while the window is open, the scan is refreshed automatically when you return to the window or press an action button (Detail Drawings, Calculation Report, PDF, Open in Connection Form); no drawing or report is produced from old results. The same applies to the options: if you change the option boxes and press an action button without pressing Scan and Design, the scan is refreshed with the new options. On rescanning, the connection selected in the list is kept. If the model has changed after the analysis, the analysis results are considered invalid (VEd = 0, status No analysis): re-run the analysis.
9.2 Which connections are found?
| Type | Recognition condition | Action |
|---|---|---|
| Beam-to-beam (T) | The beam end runs into the span of another beam, or into the splice of its two parts that continue uninterrupted at the same point. If both directions are split at the node, only the weak direction runs into the other (criteria order: section height, width, piece length); the ends of the strong direction are listed as end-to-end (splice). | Screwed design is made (if the main beam is not timber, Could not be designed). |
| Beam-to-column | The beam end is within the section of the column / post of the same storey, at an elevation along the height of the column. Posts that start from the top level of the beam (sitting on the beam) are not counted as columns. | Designed with the assumption of a screwed connection to the side face of the column. If the column is not timber or is a truss post, its section is not rectangular, the beam meets the column face at an angle (more than 15°), or the bottom end of the column is closer than 30 cm to the bottom level of the beam (short post), the status is Could not be designed; the reason is written in the breakdown. If the top end of the column is at / below the bottom level of the beam, the beam-to-beam rule is checked first: if a beam passes uninterrupted (or a stronger beam) through the node, the end runs into that beam and is designed as a beam-to-beam connection; otherwise the beam is considered to sit on the column (status Bearing, no screws needed). |
| Bearing on wall | The beam end is on top of a wall. | Listed (with VEd), outside the design scope. |
| End-to-end (corner / splice) | Two beam ends at the same point (corner, or a splice in the same direction). | Listed (with VEd), outside the design scope. |
Inclined beams and truss members (groups produced by the truss wizard) are not scanned; their nodes transfer axial force and are not the subject of this design. The number of skipped beams is written in the report. An inclined rafter is also not counted as a "main beam" for the beam it passes through at its end.
Eccentricity is taken as real. In the finite element model the nodes coincide; the real eccentricity is given in the column by the DNM / eccentricity setting, in the beam by the eccentricity setting (lateral; with the "defined axis" option on, the bar stays on the axis and the section stays to the side of the axis by the eccentricity) and the Offset settings (Bond Beam Properties › Offset: Offset2 vertical, Offset1 along the axis). If the beam axis does not pass through the middle of the column face, or the column face is narrower than the beam, the screws are placed within the overlapping width of the beam and the column face (if there is no overlap at all, the connection is not designed); if the screw group is off the beam axis, a note is made so that the moment V · e is evaluated separately. The vertical offset of the beam enters the elevation difference, and the offset along the axis enters the distance to the end of the main beam; if the end has been moved away from the main member by the offset, the connection is not designed. If, because of the vertical offset, the secondary beam lies entirely above the main beam, the connection is considered "bearing" (no screwed shear connection is needed); if there is no side face contact at all, it is not designed.
Effective number of screws in lateral shear. If the main member is a beam, the screw row is parallel to the grain of the main beam and V3 loads it parallel to the grain; therefore in calculating V3,Rd, nef,3 is taken by the EN 1995-1-1 8.3.1.1(8) / 8.5.1.1(4) rule (depending on the spacing) and cannot exceed n0.9. If the main member is a column, nef,3 = n0.9. In the report table, the "*" sign next to η shows that the ratio is the combined ratio of vertical and lateral shear.
Hanger (steel joist hanger)
The Connection box in the top row of the window offers three options: Screw; hanger if not suitable (default), Screw only, Hanger only. In the default option, a hanger is tried for connections where the screwed arrangement does not satisfy the conditions or does not fit into the section at all; if the hanger satisfies all conditions, the connection is designed with the hanger. In the list it appears in the Screw column in the form Hanger H150 12+12 Ø4x40: hanger height, number of nails in the secondary beam + in the main member, and the nail.
The calculation is generic and does not depend on a product catalogue; the dimensions, nail pattern and performance declaration (DoP / ETA) of the selected product must meet the values found. Model:
| Component | Assumption |
|---|---|
| Hanger | U-shaped sheet, t = 2 mm, fy = 250 MPa; inner width b2, height H (min(h2, top level of the main member) rounded down to 10 mm); flanges turned outward or (if the main face is narrow / the end of the main beam is close) inward. All holes are nailed. |
| Nail | Ring-shank anchor nail Ø4 × 40 / 50 / 60, fu = 600 MPa, My,Rk = 0.3 fu d2.6, fh,k = 0.082 ρk d−0.3, fax,k = 6.0 (ρk/350)² MPa (the product declaration must be at least this). In withdrawal, the ringed length lax = L − 10 − t is taken; if lax < 8d it is reduced by (lax/2d − 3) (so a 40 mm nail has half capacity in withdrawal). |
| Single nail | Steel–timber single shear, thin plate (EN 1995-1-1 Eq. 8.9); the rope effect Fax,Rk/4 cannot exceed 50% of the Johansen share. |
| Secondary beam | VRd,J = nJ · Fv,Rd (nails in the side plates). |
| Main member | In the flange nails, together with shear, the eccentricity moment V · e produces tension in the upper nails (rotation about the bottom end of the hanger): Tmax = V · e · zmax / Σz². Interaction (Fv/Fv,Rd)² + (Tmax/Fax,Rd)² ≤ 1 → VRd,H. In a column the vertical rows are parallel to the grain, so nef = nk_ef. |
| Sheet | Net shear section of the two side plates. |
| Lateral shear V3 | Shear in the main member nails and tension in the nails of one flange from the moment V3 · e; quadratic interaction with the vertical shear. When V3 is present, loaded end / edge distances (a3,t, a4,t) are checked. The behaviour of the side plate under lateral load must be verified with the product declaration. |
| Main beam | Tension perpendicular to the grain (8.1.4), he = height of the topmost flange nail from the bottom face of the main beam; b = full thickness of the main beam (EN 1995-1-1 main text; some national annexes limit the effective thickness in a connection nailed from one face). |
| Spacings | EN 1995-1-1 Table 8.2 (no pre-drilling, d < 5 mm; in a steel plate a1, a2 × 0.7): 10d from the beam end, 7d from the loaded edge, 5d from the unloaded edge; lpen ≥ 8d, lax ≥ 6d; for nails on opposite sides, thickness − lpen ≥ 4d. These spacings are for ρk ≤ 420 kg/m³; in denser material the hanger gives "Geometry condition". |
Outside the scope: the contribution of bearing on the base (not taken on the safe side), uplift, fire situation, inclined hangers (β ≠ 90°) and cases where the secondary beam extends below the main beam. When "Single detail for connections of the same section" is on, hanger connections with the same geometry share the design with the most nails. Hanger connections are not opened in the connection form; their breakdown is in the lower right part of the window and in the detail page of the report.
9.3 How is the design made?
The end of the secondary (carried) beam is connected to the side face of the main member with fully threaded screws. There are two arrangements:
| Arrangement | Description | Shear capacity |
|---|---|---|
| Crossed screw pair | In each pair, one screw works in tension (T, enters from the bottom face of the secondary beam and rises towards the main member), the other in compression (C, enters from the top face and descends towards the main member). Because it also works under load reversal, this arrangement is tried first in the Automatic option. | VRd = nef · 2 · min(FRd,T; FRd,C) · sin θ (the pair is limited by the weaker screw) |
| Inclined (tension-only) screw | All screws work in tension; the horizontal component is resisted by contact at the interface. Tried if no fully suitable solution is found with the crossed arrangement. | VRd = nef · FRd,T · sin θ |
The program tries the screw diameter (6, 8, 10, 12 mm), length, number, inclination (45°; 30° and 60° if there is no suitable solution) and the height at which the screws cross the interface, and selects the solution with the smallest screw volume that satisfies all conditions. The screw head stays at the beam surface (no countersinking). The conditions checked:
- Withdrawal strength of the threaded part in both members (ABTHYE Eq. 4.263–4.264; the grain–screw angle is taken into account),
- head embedment (Eq. 4.265) and screw tensile strength (Eq. 4.266), with effective number of screws nef = n0.9 (Eq. 4.267),
- buckling of the compression screw (beam-on-elastic-foundation approach — additional check),
- lateral shear (V3): the horizontal support shear perpendicular to the beam axis loads the screws laterally. The lateral strength of a single screw is found with the Johansen relations (single shear plane; effective diameter def = 1.1 d1; the rope effect is not taken, because the axial capacity of the screw is reserved for the vertical shear): V3,Rd = nef · ΣFv,Rd. A quadratic interaction with the vertical shear is checked: η = √(ηV² + η3²) ≤ 1 (this is the η in the list). If the lateral load is significant (η3 > 0.10), the screws are placed a4,t inside the loaded edge of the secondary beam (def < 5 mm: 7 def, otherwise 10 def),
- tension perpendicular to the grain (splitting) in the main beam — EN 1995-1-1, 8.1.4. The shears of beams running into the same section of the main beam from both sides are added (Fv,Ed); if this check governs, the height at which the tension screw crosses the interface (he) is reselected accordingly,
- geometry conditions (Table 4.24): a2 ≥ 5d; if the main member is a beam, the same row is laid out in the grain direction of the main beam, so a1 ≥ 7d; a2,CG ≥ 4d (in the secondary, the side and bottom/top edge; in the main beam, the bottom and top edge), a1,CG ≥ 10d (secondary beam end, column top end, physical end of the main beam: if the main beam does not continue at that end or is cut at the side face of a column — even if another piece continues in the same direction — the distance is checked to the column / beam face; it is not checked only at a model split and for a continuous beam sitting on a column), lef ≥ 6d, t ≥ 12d, 6 ≤ d ≤ 12 mm, screw inclination ≥ 30°. A single screw is not used in the inclined (tension-only) arrangement.
The geometry conditions are a hard rule: if strength is not sufficient with an arrangement that satisfies the conditions, the status is Inadequate; the program does not select an arrangement that violates the conditions in order to reach the strength. If no arrangement fits the section while satisfying the conditions, the status is Geometry condition.
| Input | Source |
|---|---|
| VEd, V3,Ed | The vertical (V2) and lateral (V3) support shear at that end of the beam: the value of the combination governing in the member check. V2 and V3 are taken from the same combination; the governing combinations of V2 and of V3 are checked separately, and the one governing the design is shown. The name of the combination is written in the breakdown and in the report. The load factors are the G and Q factors in Project General Settings (1.0 / 1.0 in a new project; 1.35 / 1.5 must be entered for limit state design). |
| kmod | cy × CN. cy: load duration factor of the governing combination (vertical load combination 0.8; seismic combinations 1.1; in user-defined combinations 1.1 / 0.8 / 0.6 according to the duration of the loading). CN: the member's own moisture selection (Beam / Column Properties: Low 1.00 – Medium 0.95 – High 0.85); the smaller of the secondary beam and the main member is taken — the same assumption as in the member check. If there is no analysis result, cy = 0.80 is assumed and a note is made. If desired, a fixed kmod can be selected in the window. |
| ρk, sections, elevations | Timber material assigned to the members and the model geometry. |
| Screw properties | Generic fully threaded carbon steel screw assumption (d1 = 0.65d, dh = 1.8d, ftens,k = 800 MPa × root area, fhead,k = 10 MPa, fy,k = 1000 MPa). In practice it must be verified with the performance declaration (DoP / ETA) values of the selected product. |
9.4 Window
| Section | Content |
|---|---|
| Options | Screw arrangement (Automatic / Crossed pair / Inclined), diameter range, inclination (Automatic / 45° / 30° / 60°), kmod (from analysis or fixed), γM; Single detail for connections of the same section (on): connections with the same sections, elevations and angle are collected in a group and designed with a single screw arrangement according to the most unfavourable connection of the group; each connection is re-evaluated with its own force. If it is turned off, each connection is designed separately according to its own force (many detail types result); Columns continuous between storeys (off): if turned on, a timber column continuing at the same point in the upper storey is assumed to be continuous (unspliced), and the column top end distance condition is checked to the top end of that column. If columns are spliced at the storey level (platform-framed systems), leave it off; Selected beams only: the list contains only the ends of the beams selected in the plan (the scan is still made on all beams; the shear of a neighbouring beam running into the same section is included in the calculation); Active storey only. |
| Connection list | Storey, beam and its end (I: start end of the beam, J: end end), main member, type, VEd, selected screw (e.g. 2 x 2 Ø6x260 = 2 pairs; in the inclined arrangement 2 Ø6x200 = 2 pieces), arrangement and inclination, VRd, utilisation ratio η (the larger of the shear and tension-perpendicular-to-grain ratios), status and detail type (D1, D2 …). The "!" sign next to the status shows that there is a warning specific to that connection (screws entering from the opposite face, axis offset in the model, narrow column face …); when the row is selected, it can be read in the Note lines of the breakdown. |
| Preview and breakdown | Section + plan detail of the selected connection, and the breakdown of inputs (combination name, kmod), single screw strengths, governing failure mode, connection strength and geometry conditions ([+] satisfied, [X] not satisfied). |
| Status | Meaning |
|---|---|
| Suitable | All strength and geometry conditions are satisfied. |
| Inadequate | Strength cannot be achieved even with the strongest arrangement that complies with the geometry conditions (η > 1; the tension-perpendicular-to-grain ratio is included). Enlarge the section or use a hanger / steel fastener. |
| Geometry condition | No screw arrangement fits the section while satisfying the spacing / edge / end distance conditions; the condition not satisfied is shown with [X] in the breakdown. |
| No analysis | There is no current analysis result: the smallest (constructive) arrangement has been assigned with VEd = 0. Run the analysis and rescan. |
| Bearing | The beam sits on top of the column; no screwed shear connection is needed (the bearing check is in the member calculation). |
| Could not be designed | A beam-to-beam / beam-to-column connection that cannot be designed: the main member is not timber, the angle between the axes is less than 30°, or no screw fits the section. The reason is in the Note line of the breakdown. |
| Out of scope | Bearing on a wall and end-to-end (corner / splice) connections. |
9.5 Detail drawings and calculation report
- Main calculation report: with the Timber Connections - Automatic Design Summary (Specification 2024, 4.11) box ticked under the Timber group in the Report Selection window, a summary page is added to the main report: design options, numbers of connections, for each detail type the connection label, quantity, status, the forces and ratios of the most unfavourable connection and where it is applied. If no scan has been made, or the model / analysis has changed, it is refreshed automatically with the last options while the report is produced. The detailed calculation breakdown and detail pages are under the Calculation Report button below.
- Detail Drawings: connections sharing the same section and the same screw arrangement are collected in one detail type; for each type, the section and plan view, its dimensions, the screw label and the list of places where it is applied are transferred to the drawing screen; on the right, a connection layout plan is drawn for each storey (beam axes, columns, detail number at the ends; unsuitable ones in red, those that could not be designed "?"). Tension screws are on the AhsapVidaT layer (red), compression screws on the AhsapVidaC layer. The command opens the drawing screen itself and starts a new drawing; save any unsaved drawing on the screen first.
- Calculation Report: assumptions and options used, table of detail types, reasons for connections not designed, list of all connections (those with a connection-specific warning are marked with "!") and a calculation page with drawings for each detail type (inputs, governing combination, geometry conditions, single screw strengths, connection strength, tension perpendicular to the grain, places where applied, lateral shear check, the notes of all connections of that type, relations used). The PDF… button writes the report directly to a file (fonts are embedded).
- Open in Connection Form: opens the selected connection in the connection form described in Sections 1–7. The form is set to Screwed (axial) mode and the axial check of the tension screw group of the designed connection is filled in with the design values and calculated: d, root diameter, ftens,k, lef and grain angle in the governing member, n, kmod, γM and the axial force on the group Fax,Ed = VEd / (2 sin θ) (VEd / sin θ in the inclined arrangement). If the tension screw governs, the utilisation ratio in the form is the same as η in the automatic design; if the compression screw (buckling) governs, the form shows a smaller ratio (the form checks only the tension screw).
9.6 Limits
- The axial tension force of the beam is included in the design: N is taken from the same combination as V2 / V3; in addition, the combination governing the tension (with its V2, V3) is checked as a third load case. In a crossed pair, the tension screw carries V/(2 sin θ) + N/(2 cos θ) and the compression screw V/(2 sin θ) − N/(2 cos θ) (if the sign changes, it is checked with the tensile strength); in an inclined arrangement the screw force is taken as max(V/sin θ, N/cos θ). In a hanger, N is added as resultant shear to the secondary beam nails and as additional tension N/nH to the main member nails. Condition: if a vertical eccentricity (offset) of the beam is modelled in the finite element model (with the eccentricity / offset options in Project General Settings on, the beam axis is h/2 below the node), the axial force of the FEM contains an artificial "composite" effect; in this case the axial force is not taken into the design, and the raw value read is shown as information in the breakdown. Axial compression is transferred by contact and is not loaded onto the connection elements. Lateral shear (V3) is included; in a beam connected to a column this force loads the column perpendicular to the grain, and the check of the column under this force is in the member calculation (a note is made).
- The screws are first placed as a single row across the beam width. If there is no arrangement with a single row that satisfies all conditions and the Two rows of screws if needed box is ticked (default), a second row is tried in the height direction: the same screw, the same inclination; the vertical spacing between rows from EN 1995-1-1 Table 8.6 (in the secondary beam a1 = 7d in the grain direction, in the main beam a2 = 5d perpendicular to the screw axis, in the column a1 = 7d in the grain direction). Effective number (n × rows)0.9; since the two rows share the length differently, the smaller of the rows is taken as the single screw strength. In the list,
2 x 2 x 2 Ø6x260= 2 rows × 2 pairs × 2 screws. In low sections (h ≈ 150 mm), the second row often does not fit or its length in the main member remains short; if two rows are also not enough, the status is Inadequate (a hanger is tried depending on the connection option). - It must be checked in practice that screws entering a main member from opposite or adjacent faces do not collide; if a beam also runs in from the opposite face and the screws exceed half the width of the main beam, the program makes a note (staggering).
- For the bottom end of the column no end distance is checked (the beams are at the top of the storey); for the top end of the column see Columns continuous between storeys.
- The design results are not saved in the project file; the window rescans the model every time it opens.
- The automatic design does not change the member calculations and the analysis results.