This article summarises which code rules the StatiCAD steel beam and column design module applies and which assumptions it makes. The rule set used is ÇYTHYE (Turkish Design, Calculation and Construction Principles for Steel Structures) and the provisions of TBDY 2018 relating to steel. For usage see Steel Beam and Column Design.

info

Design approach: LRFD (Load and Resistance Factor Design). Resistance factors: flexure φb = 0.90; shear φv = 0.90 (1.00 for a compact rolled I web); compression φc = 0.90.

1. Material and section properties​

The steel grade is assigned to the member together with the section; Fy and E are read from the material library. Section properties (A, Ix, Iy, Wel = Sx, Wpl = Zx, Zy, Sy, J, Cw, h, b, tf, tw, r) are taken from the prefabricated section database. The modulus of elasticity in the material library may be defined in kg/cm² or MPa; the program recognises the unit automatically.

2. Beam flexural strength (Chapter 9)​

For doubly symmetric rolled I/H beams bending about their strong axis, three regions are defined (Lb: laterally unbraced length):

RegionConditionNominal strength Mn
Yielding (plastic)Lb ≤ LpMp = Fy·Zx
Inelastic lateral–torsional bucklingLp < Lb ≤ LrMn = Cb·[Mp − (Mp − 0.7·Fy·Sx)·(Lb − Lp)/(Lr − Lp)] ≤ Mp
Elastic lateral–torsional bucklingLb > LrMn = Fcr·Sx ≤ Mp
info
  • Lp = 1.76·ry·√(E/Fy)
  • Fcr = Cb·π²·E/(Lb/rts)² · √(1 + 0.078·(J·c/(Sx·h0))·(Lb/rts)²)
  • Lr = 1.95·rts·(E/(0.7·Fy))·√(J·c/(Sx·h0) + √((J·c/(Sx·h0))² + 6.76·(0.7·Fy/E)²))
  • rts² = √(Iy·Cw)/Sx, h0 = h − tf, c = 1 (doubly symmetric I)

The report shows Lp, Lr and the name of the governing limit state, so that the consistency of Lb with the limit state can be checked by the engineer. The flexural compactness of the cross-section is classified; for a non-compact flange the local flange buckling limit state comes into play.

2.1 Unbraced length Lb and moment modification factor Cb​

Lb is the length of the compression flange that is laterally unbraced (ÇYTHYE 9.2.2). If the lateral support (Le) fields in the member properties are left automatic, Lb = member length L (between its end nodes) is used and the ends are assumed to be laterally braced (ÇYTHYE 9.1(a)). If there is intermediate lateral bracing, the largest unbraced length is entered manually in the Le field.

info
  • Cb = 12.5·Mmax / (2.5·Mmax + 3·MA + 4·MB + 3·MC) (ÇYTHYE Eq. 9.1), 1.0 ≤ Cb ≤ 3.0
  • Mmax, MA, MB, MC: absolute values of the largest moment along the unbraced length and of the moments at the 1/4, 1/2 and 3/4 points

The moments are taken from the beam stations (segment ends) of the finite element solution; the values at the quarter points are found by linear interpolation between adjacent stations.

  • Each strength combination is checked with its own moment diagram. Because Cb varies with the combination, the governing combination is not the one giving the largest moment but the one with the largest demand/capacity ratio. In the report the design moment, the combination name and Cb belong to this combination; shear and axial force are taken from the envelope.
  • Cantilever (a member with one end not connected to a column, wall or another beam): Lb = L and Cb = 1.0 (ÇYTHYE 9.1(e)).
  • The end of a secondary beam framing into another beam is treated as a support, like a column or wall support; Cb is calculated from the diagram.
  • If a Lb shorter than L is entered in the Le field (intermediate bracing; the moment diagram of the unbraced segment is not separately known), or the beam is divided into fewer than 4 finite element segments, Cb = 1.0 is used (safe side).

3. Beam shear strength (Chapter 10)​

info

Vn = 0.6·Fy·Aw·Cv1, Aw = d·tw

If h/tw ≤ 2.24·√(E/Fy) is satisfied for a rolled I web, Cv1 = 1.0 and φv = 1.00 are used; otherwise the general web rules are applied.

4. Combined effect in beams (Chapter 11)​

The interaction of flexure, shear and axial force is checked and written to the report as a single ratio; if the ratio is ≤ 1.0, UYGUN (OK) is marked.

5. Beam deflection​

info

f = 5/48 · Mmax · L² / (E·Ix) (simple beam, uniformly distributed load equivalent); condition f ≤ L/K.

Mmax is the service moment: the largest of the unfactored G+Q and G+S combinations. For a cantilever beam the coefficient 1/3 is used instead of 5/48 (tip-load equivalent; conservative for a distributed load). K comes from the deflection K selection in the member properties (default 300; 200 / 150 / manual).

6. Column compressive strength (Chapter 8)​

For a doubly symmetric I/H compression member, three elastic buckling stresses are calculated and the smallest governs:

info
  • Flexural: Fex = π²·E/(KLx/rx)², Fey = π²·E/(KLy/ry)²
  • Torsional: Fez = [π²·E·Cw/(KLz)² + G·J] / (Ix + Iy), G = E/2.6
  • Fe = min(Fex, Fey, Fez)
  • Fy/Fe ≤ 2.25 → Fcr = 0.658^(Fy/Fe) · Fy (inelastic); Fy/Fe > 2.25 → Fcr = 0.877·Fe (elastic)
  • Pn = Fcr·Ag, φc = 0.90

The governing mode is stated in the report. The weak-axis length is used for the torsional buckling length.

Effective buckling length: By default KL = storey height + the bottom/top level differences of the member, K = 1.0. A separate length can be defined for each axis by entering K·L manually in the Le fields of the vertical bond beam window. If KL/r > 200, a red warning is written to the report (the calculation is not stopped).

Cross-section slenderness (Table 5.1A, axial compression): Flange b/(2·tf) ≤ 0.56·√(E/Fy); web hw/tw ≤ 1.49·√(E/Fy). For a cross-section exceeding the limit (slender), the effective area method (ÇYTHYE 8.4) is not applied: if the member has a compression demand (|N| > 1 kN), the compression side is not passed, 99 is written as the interaction ratio, and the member is marked “narin enkesit” (slender cross-section) in the report and is considered inadequate. The section properties, the flexure and shear capacities, and the tension–flexure interaction (Eq. 11.3a/b, Pc = 0.90·Fy·Ag) are still calculated. The rule is applied in the same way to columns and to beams under axial compression (truss top chord, purlin, etc.).

7. Column weak-axis flexural capacity​

info

Mny = Fy·Zy ≤ 1.6·Fy·Sy (lateral–torsional buckling does not occur about the weak axis).

8. Combined effect in columns (Chapter 11.3)​

info
  • Pr/Pc ≥ 0.2: Pr/Pc + 8/9·(Mrx/Mcx + Mry/Mcy) ≤ 1.0 (11.3a)
  • Pr/Pc < 0.2: Pr/(2·Pc) + (Mrx/Mcx + Mry/Mcy) ≤ 1.0 (11.3b)

Pc = φc·Pn; Mcx is the strong-axis capacity including lateral–torsional buckling (Lb = KLy, Cb = 1.0), and Mcy is calculated with the weak-axis rule. The equation used is stated in the report.

9. Internal forces and load combinations​

For the beam M, V (and N), and for the column N, Mx, My and V are taken from the program's finite element solution as the envelope of the following combinations:

  • The program's combinations, as converted for steel design: in combinations with earthquake, 1.0G → 1.2G and Q at least 1.0Q (TBDY 4.4.4.2). The names of these combinations appear in the report with the suffix “[1.2G+1.0Q]”.
  • ÇYTHYE LRFD combinations (from the plain G, Q, S, W load cases): 1.4G; 1.2G + 1.6Q (+0.5S); 1.2G + 1.6S (+1.0Q); if wind is defined, for each wind case 1.2G + 1.6S + 0.8W, 1.2G + 1.0Q (+0.5S) + 1.6W and 0.9G + 1.6W.

If no wind load case is defined, an analysis warning is given. The name of the combination that gives the envelope is shown next to the demand in the report.

9.1 Artificial axial force caused by the offset​

If Take Offset1 and Offset2 values into account in the system stiffness matrix or, with a defined axis, Take eccentricities into account in the system stiffness matrix is ticked in Project General Settings, the beam axis is modelled lower than the joint axis by e2 = offset2 − h/2. Because the rigid diaphragm or the supports restrain the axial displacement of the joints, an axial force that does not exist in reality arises in the beam (the effect of a composite section with an infinitely rigid flange). This force is constant in each chain between diaphragm joints:

info
  • Nk = ck · M̄3, ck = A·e2 / (I3 + A·e2²)
  • M̄3: length-weighted average moment along the chain; M3 is the total moment about the joint axis.

For IPE 300 (A = 53.81 cm², I3 = 8356 cm⁴, e2 = −15 cm), ck = −3.944 m⁻¹; the finite element segment forces reproduce this value to four-digit accuracy. Without this subtraction, the force reaches 318–721 kN in the test models and increases the M–N–V ratio by about 30%. As with cold-formed steel beams, the program subtracts this share from the segment axial force of each load case (see Theoretical Basis of Cold-Formed Steel Design, Section 12): the moment does not change; the subtracted share does not exceed |N| and does not reverse its sign; chains are recognised from consecutive segments with equal N (if the “Do not connect beam intermediate joints to the rigid diaphragm” option is ticked, the whole beam is a single chain). The remaining axial force is the trapezoidal-rule remainder arising from the average of the end moments ((2/3)/n² of the peak value under a distributed load; 0.5% with 12 segments, on the safe side). The effect of the offset on the beam stiffness is a model result and is retained: in a rigid-ended beam the end moments may come out larger with the offset on (84.8 kNm against 74.5 kNm in one example).

10. Truss members and other section types​

For the design check of steel roof trusses and purlins, the beam and column checks have been extended with the following rules:

  • Axial compression buckling in beams: φcPn from Section 6 is calculated with KLx = KLy = the member length from node to node (the three-dimensional length for an inclined member), and the axial force–flexure interaction of Eq. 11.3a/b is applied. The reported ratio is the larger of Eq. 11.11 and Eq. 11.3. Because the axial force envelope of the beam is unsigned, the axial force is assumed to be compression (on the safe side in tension).
  • Axial tension in columns and posts: For the tension envelope (LRFD combinations), yielding on the gross section φtTn = 0.90·Fy·Ag and the tension–flexure interaction (Eq. 11.3a/b) are checked; the governing (compression or tension) interaction is reported. Rupture on the net section (ÇYTHYE Chapter 7) is a matter of connection design.
  • Other section types: U (ÇYTHYE 9.2; for a channel c = (h₀/2)·√(Iz/Cw)), box (9.7; lateral–torsional buckling is not considered), pipe (9.8; D/t > 0.45E/Fy is outside the scope) and equal-leg L (9.10; Mcr from Eq. 9.69a; if J is not in the catalogue, (1/3)·Σbt³). The shear strength is calculated with the section-type cases of Chapter 10 (10.3 box, 10.4 pipe, 10.5 L and T). In compression, flexural buckling of the L section is calculated with the principal-axis moments of inertia. Cross-section slenderness is checked with the section-type limits of Table 5.1A (box 1.40; pipe 0.11E/Fy; L 0.45; U flange 0.56, web 1.49).
  • Design wall thickness of pipe and box sections (ÇYTHYE 5.4.2): The design wall thickness is used in section calculations: td = 0.93·t for electric resistance welded (ERW, TS EN 10219) members and td = t for submerged arc welded members. ERW is the default; the selection is made in the Project General Settings → Code Selection → Pipe/Box Section Production box and is saved with the project. The cross-section properties are recalculated from the geometry with td: for a pipe A, I, W, Wp and J with closed formulas; for a box A, I, W, Wp and Bredt J = 4·Am²·t/p as the difference between the outer and inner rectangles, with the outer corner radius 2·td and the inner corner radius td (corner voids subtracted). This assumption matches ÇYTHYE Application Guide Example 9.8 (box 200×200×8: We = 341, Wp = 400 cm³) exactly. The local buckling width is b = B − 3·td.
  • Geometric-axis bending of an equal-leg angle (ÇYTHYE 9.10.2(2)(i)): For an equal-leg angle that is not continuously restrained against lateral–torsional buckling, the yield moment is taken as My = 0.80·Fy·We (geometric axis); this My is used both at the yielding limit (9.65: 1.5·My) and in 9.66/9.67. Mcr is calculated with Eq. 9.69a for the leg tip in compression (9.69b for tension is larger; the program uses 9.69a on the safe side), Cb ≤ 1.5. Leg local buckling (9.10.3) is checked with the geometric-axis We.

Torsional constant in the finite element model: In beams with steel and light-gauge steel profile sections, the true St-Venant J is used as the torsional constant instead of the polar moment of inertia (I₂ + I₃); in columns and posts with profile sections, J (cm⁴) from the section library is taken with the correct unit. For types without J in the catalogue, J is derived: for a box, the closed-section (Bredt) formula J = 2t(h − t)²(b − t)²/((h − t) + (b − t)); for L, T and U open sections, J = (1/3)·Σbt³. In reinforced concrete beams with circular, T, L, I and polygon sections, the true J from the section library is also used; for polygon sections the Saint-Venant approximation J = A⁴/(4π²(I₂ + I₃)) is applied (exact for a circle, a good approximation for solid polygons, on the safe side for a section with voids). The section editor also writes this approximation to the J field of polygon sections. In precast variable-section (nonprismatic) beams the polar moment of inertia is still used. J is saved with the project file; in projects without a J record it is derived again from the steel catalogue.

Modulus of elasticity in the finite element model: If the steel E on the material card is stored in kg/cm², its unit is recognised and converted in the design and in the finite element model. In the steel records of the library E = 200,000 MPa (ÇYTHYE); in old projects the copy on the card may have remained at the old value (2,100,000 kg/cm²). The material form shows the unit of the steel E row.

note

Deliberate limits: Flexural–torsional buckling of U sections in compression (the shear centre data is not in the catalogue) and the equivalent slenderness of L sections are not considered; in flexure, a U section whose flange is not compact is marked “desteklenmiyor” (not supported). Because the section properties of T sections are empty in the catalogue, T sections are outside the scope.

11. TBDY 2018 Chapter 9 rules​

  • System and ductility level: R, D, BYS and the ductility level are taken from the Table 4.1 group C code (C11–C33); the level of the moment frame members is high in C1x and limited in C2x and C3x (braces and shear wall are high in a composite system). If there is no C code, the project ductility setting is used (composite → limited).
  • Table 9.3 section compactness requirement: The b/t definitions are the same as in ÇYTHYE Table 5.1 (I/H flange bf/2tf, U flange b/tf, web h = H − 2(tf + r), box b = B − 3t, angle longest leg/t, pipe D/t; the ÇYTHYE 5.4.2 design wall thickness for pipes and boxes). The limits (high / limited): flange 0.30·√(E/Fy) / 0.38·√(E/Fy); box 0.55·√(E/Fy) / 1.12·√(E/Fy); pipe 0.038·E/Fy / 0.07·E/Fy; web, with Ca = Pu/(0.90·Fy·A), for Ca ≤ 0.125 2.45·√(E/Fy)·(1 − 0.93·Ca) / 3.76·√(E/Fy)·(1 − 2.75·Ca), otherwise 0.77·√(E/Fy)·(2.93 − Ca) / 1.12·√(E/Fy)·(2.33 − Ca) ≥ 1.49·√(E/Fy). Pu is the compression value of the envelope for a beam and Nd for a column. The requirement applies to steel columns (except truss posts) and to beams with moment transfer at at least one end.
  • Lateral bracing spacing (9.2.8.1): Lb,max = 0.086·iy·E/Fy (high) / 0.17·iy·E/Fy (limited); iy is the weak-axis radius of gyration. The Lb compared is the length used in the lateral–torsional buckling calculation.
  • Material (9.2.3.1(a), Table 9.2): A warning is given for Fy ≤ 355 in a beam and Fy ≤ 460 MPa in a system column (except the column of a limited ductility level moment frame). Ry/Rt are taken from the material name: S235 1.4/1.1; S275 1.3/1.1; S355 1.25/1.1; S460 1.1/1.1; pipe and box 1.4/1.3.
  • Combinations amplified by D (9.2.6): The program's seismic combinations are copied with the LRFD conversion (in the seismic combination 1.0G → 1.2G, Q at least 1.0Q; 0.9G ± E unchanged), and the coefficient of the horizontal earthquake loadings is multiplied by DX in the X direction and DY in the Y direction. The vertical earthquake is not multiplied. For rigid basement storeys the basement D of Eq. 4.6 is used. The mechanism (capacity) upper limit is not applied; the result is conservative.
  • D·E axial check in a column (9.3.1.3(b) / 9.4.1.3): In steel columns of the lateral load resisting system (except truss posts), with M = 0, Nu = max(D·E compression) ≤ φc·Pn (Section 6, with the same KL) and Tu = max(D·E tension) ≤ φt·Tn = 0.90·Fy·Ag; the two ends are scanned separately.
  • Foundation connection (9.12, information): At the bottom end of a storey 1 column, or of the first storey column above a rigid basement, N (compression, tension), V2, V3 and M = min(1.1·Ry·Fy·Wp; MD·E) are taken from the D·E envelope (each axis separately).
  • Shear method: Since EX/EY are not solved in the finite element model in the classical method, if the project contains a heavy steel beam or column, the shear and vertical load method is taken into finite elements in the analysis (information line).
  • Joint matching: The beam end–column matching is taken from the beam support detection, and the upper storey column from the load transfer between storeys. If the beam direction is within ≤ 45° of the XK1–XK2 direction of the column, it is the strong-axis (M3) frame of the column. Whether a steel beam end is considered hinged is determined by the end release in the finite element definition.
  • Required connection strength (9.3.4.1(b,c), information): Mpr = 1.1·Ry·Fy·Wp; ℓn = L − dc,left/2 − dc,right/2 (dc: depth of the column in the beam direction; ℓn ≥ 0.5·L); Vuc = |Vd| + (Mpr,i + Mpr,j)/ℓn (Mpr = 0 at a hinged end; Vd is the beam end shear of 1.2G + 0.5Q + 0.2S); since the hinge is assumed at the column face, Muc = Mpr.
  • Strong column (9.3.2): ΣM*pc = Σ Wpc·(Fyc − Puc/Ag) (Eq. 9.8b; lower column + upper storey steel columns; Puc is the D·E compression, otherwise the LRFD envelope; 0 if the parenthesis is negative), ΣM*pb = Σ(1.1·Ry·Fyb·Wpb + Muv), Muv = Vuc·dc/2 (Eq. 9.9b). Column moments are not moved to the joint centre (conservative). Each axis is checked separately; if the ratio is ≤ 1.0 the column is Inadequate. 9.3.3.1(a): if Pu (LRFD envelope) < 0.3·Fy·Ag and (there is no upper column or the building is single-storey), the column is exempt. It is applied only when the frame ductility level is high.
  • Panel zone (9.3.4.2 / 9.4.2.2, I/H column): Vup = Σ Mi/(db,i − tbf,i) − ΣMi/Hort; Mi = Muc (high) or min(beam design moment envelope; Mpr) (limited; the envelope may also include the span moment, conservative); Hort is the average of the lower and upper storey column lengths. φv·Rn = 1.0·0.6·Fy·(dc·tw + 3·bcf·tcf²/db) (panel zone deformation taken into account); if Pr > 0.75·Py the strength is multiplied by kP = 1.9 − 1.2·Pr/Py. Required total thickness t = (Vup/(0.6·Fy·kP) − 3·bcf·tcf²/db)/dc, doubler td = t − tw; u = 2[(db − 2·tbf) + (dc − 2·tcf)], tw ≥ u/180.
  • Continuity plate (9.3.4.3): For strong-axis beams, tcf ≥ 0.4·√(1.8·bbf·tbf·Ryb·Fyb/(Ryc·Fyc)) and tcf ≥ bbf/6 (the most unfavourable beam); if not satisfied a plate is required, t ≥ max tbf.
  • Lateral bracing force and column splice (9.3.6(a), 9.3.5, information): The lateral bracing force is 0.02·Fyb·bbf·tbf (largest beam; only at the top flange level if the strong column ratio is > 2.0); the bolted upper column splice is M = min(Ry·Fy·Wp) (lower / upper column), V = 2·Wp·(Fy − Pu/A)/Hc (upper column). The unbraced joint of 9.3.6(b) is not recognised from the model.
  • Concentric brace (9.5–9.7): Layout (Figure 9.5): if the end is at the storey level and at the column section, a column joint; in the beam span (2–98%), inverted V (upper end) / V (lower end); at the column section between storeys, K (prohibited, Inadequate); if it is at the end of another brace or has a counterpart with the opposite inclination in the same vertical plane, X; otherwise diagonal. Slenderness KL/i: L is the three-dimensional length (the user's buckling length if entered), i = √(Imin/A) (principal for an angle); the limit is 200, and 4·√(E/Fy) for limited ductility level V / inverted V. Fcre: the ÇYTHYE 8.2 curve with Ry·Fy instead of Fy; T = Ry·Fy·Ag, P1 = 1.14·Fcre·Ag, P2 = 0.3·P1. 9.6.6: tension Ry·Fy·Ag, compression 1.1·min(Ry·Fy·Ag; 1.14·Fcre·Ag), flexure 1.1·Ry·Mp (smaller Wp). 9.6.3.4: Ae ≥ Ry·Fy·Ag/(Rt·Fu). 9.6.1.2: braces on the same storey with a plan direction difference < 5° and an axis distance < 100 cm form one axis; in the earthquake loading that gives the larger horizontal force in the axis direction, the share of the compression braces in Σ|P·cos α| must be 0.30–0.70. The brace ductility level is the brace ductility of the C code (the higher one if it differs in the two directions); if there is no C code, the project setting is taken. The brace rows of Table 9.3 are applied; 9.2.8.1 and deflection are not checked; the brace does not enter the strong column joint calculation.
  • Column and beam of the braced frame (9.6.2, 9.6.4.1, 9.7.2, 9.7.4.1): The braces are separated into EX or EY according to their plan direction; the tension/compression state of a brace for one earthquake direction and sign is found from the sign of the axial force in the loading of that direction. Mechanism (a): tension T, compression P1; (b): T and P2. The force acting on the end joint is F·u (u: unit vector from the end to the other end). The column mechanism axial share is the sum of the contributions of the brace ends falling on the column section at the storey and the levels above (9.6.2.3 joint equilibrium); the vertical force of the ends connected to a V beam is distributed to the beam ends by weight. In each D·E combination the dominant direction and sign are selected; N = Nvertical + sign(Nmech)·min(|Nmech|; |ND·E|) (9.6.2.4); if Nmech and ND·E have opposite signs or Nmech = 0, ND·E is taken. Mx, My and V are the D·E envelope at the two ends; in limited, N, M and V are the D·E envelope. The check is made with the normal column check (ÇYTHYE 8 + 11.3, the same buckling lengths). Bay beam with a brace: D·E envelope (N, M3, V2; Cb = 1) and Table 9.3 (brace ductility). V / inverted V beam: a simple beam with the braces removed; the vertical load is distributed per piece, with the non-seismic coefficients of the D·E combination; at the brace point Pz = −Σ F·uz (downward +), beam axial force |Σ F·uh|/2 (assumed compression). In high, F = T, −P1 / −P2 (9.6.4.1(c)); in limited, F = min(T; D·E tension), −0.3·Fcr·Ag. Lb is the largest spacing between the ends and the brace points.
  • Axial force of a bay beam with a brace (9.6.2.4): In high ductility, in each D·E combination N = NG + r·NE; r = min(1; max(Fmech,i/|FDE,i|)), i the braces connected to the beam; FDE,i is the seismic share of the brace amplified by D in that combination, Fmech = T (tension) or P1/P2 (compression; cases a and b separate). M and V are taken from the D·E envelope. There is no change in limited ductility level (9.7.2).
  • Brace–beam–column connection (9.6.5, information; high ductility only): The end is marked if the beam end is connected to a steel column at the storey level and there is a brace end at the same joint in the same vertical plane as the beam (plan direction difference < 5°). Hinged end: a rotation of at least 0.025 rad (Annex 9C). Rigid end: M = min(1.1·Ry·Fy·Zbeam; Σ 1.1·Ry·Fy·Zcolumn); the columns are the lower column and the upper column, Z is about the axis in the beam direction (column strong if ≤ 45° to the XK direction). LRFD.
  • Diaphragm collector and horizontal brace (9.10.3 / 9.10.4): Horizontal brace: “Steel brace” ticked and |z2 − z1| ≤ max(10 cm; 0.05·Lplan). Beam of the horizontal brace system: its end is within 15 cm of a horizontal brace end on the same storey. Collector: plan direction difference < 5° from the vertical brace axis, perpendicular distance of its midpoint from the axis < 100 cm, the storey level is the level of a brace end, and it is not a bay beam with a brace. Check: beam check with the N, M3, V2 envelope at the piece ends from the D·E combinations (Lb of the normal design, Cb = 1); Nbas/Nçek is reported as the required connection strength.
  • Tension-only brace (9.6.4.3 / 9.7.4.3): In the finite element model the axial area is taken as A/2 (mass preserved); in a symmetric X the total lateral stiffness of the two braces equals that of a single tension brace. In design, the group: same storey, plan direction difference < 5°, axis perpendicular distance < 100 cm. In each combination N = NG + NE (horizontal earthquake loadings; with D in D·E); Ht = Σ|NE|·cos θ (NE tension), Hc = ΣNE·cos θ (compression), f = (Ht + Hc)/Ht; tension brace NG + f·NE, compression brace NG; 0 (slack) if the total is compression. Tu ≤ 0.90·Fy·Ag and 11.3 (tension + M3/Md); there is no compression buckling in the member design. KL/i ≤ 300; the 9.7.5 compression limit is 0; in a V beam the compression brace is 0. Inadequate in high ductility level (9.6.4.3); Inadequate if the group has no opposite inclination. Since the catalogue has no rod or cable sections, the exception to the limit of 300 is not applied. Horizontal tension-only brace: The finite element area is again A/2; the group consists of braces crossing at an interior point in plan on the same storey; the same transfer formula is used. The design force is the tension transferred, max(LRFD; D·E) (9.10.4); the 9.6.4.3 prohibition and KL/i ≤ 300 are not applied.
  • Diaphragm chord (9.10.2): For the storey top slab and each horizontal earthquake loading, the transfer forces Ri: the top section shear of the shear wall/column − the bottom section shear of its continuation on the upper storey, and −P·uhorizontal at the concentric brace end at the storey level (P > 0 compression); ΣR = F. The inertia F is proportional to the area of the slabs. The diaphragm boundary is the slabs and the transfer points. At section s, M(s) = F·Σap(s − sp)/A − Σ[Ri,perp·(s − si) + Ri,axis·(ti − tc)] (those to the left of s; components in the span direction as a force couple about the mid-depth); 100 sections; T = |M|/B. Chord beam: a horizontal steel beam (not a brace), within < 5° of the span direction, with its midpoint within max(100 cm; 0.05·B) of the outer edge; the largest T in the sections it covers is added to the ÇYTHYE envelope axial force (|N| + T compression; the envelope also includes the non-seismic combinations, conservative). Reinforced concrete slab: σ = M/(h·B²/6) ≤ 0.20·fck, As = T/fyd (information).
  • Space roof truss (9.10.4): In the groups created by the roof and truss wizards, a group is considered a space truss if the largest distance of the plan end points of all members of the group from the line through the two farthest points is > 20 cm. Steel beams enter the beam check with the D·E envelope, and truss posts enter the column check with the axial force amplified by D.

12. Scope limits​

  • The load-bearing capacity check covers I/H, U, box, pipe and equal-leg L sections (Section 10); T sections and unequal-leg angles are marked “desteklenmiyor” (not supported) in the report.
  • The design of cold-formed sections is performed in the light-gauge steel module.
  • In beams Cb is calculated from the moment diagram of the combination (Section 2.1); Cb = 1.0 is used for strong-axis bending of columns. For columns K = 1.0 is assumed; different support conditions are provided by the user through the Le fields.
  • There is no effective area method for slender cross-sections, and no torsional–flexural buckling of singly symmetric sections.
  • The eccentrically braced frame (TBDY 9.8), the buckling-restrained brace (9.9) and the composite column (9.11) are outside the scope.
  • Lateral support in a beam is taken as a single length; there is no definition of an intermediate support list (Cb = 1.0 for a beam with intermediate bracing). The automatic Lb is the length between end nodes: for a beam divided into segments without intermediate supports in the same direction, the real unbraced length must be entered in the Le field.