Cold-Formed Steel Panel and Stud Design
This article describes the use of StatiCAD’s cold-formed (light-gauge) steel shear wall panel module. The module performs two main checks: the panel’s sheathing shear capacity (TBDY 2018) and the studs in the panel frame under axial compression plus out-of-plane wind bending (Effective Width Method — EWM in the layout of HCBTİE Chapter 4; LRFD or ASD). The forces are taken from the program’s analysis solution; results are presented in the analysis warnings and in the Turkish/English calculation reports.
Related articles: Cold-Formed Steel Program Menus (illustrated description of all windows and inputs), Cold-Formed Steel Beam and Column Design, Code Requirements, Anchorage and Foundation, Theoretical Basis, Verification.
Which editions? Cold-formed steel calculations are available in the StatiCAD Ultimate edition. Panel data is stored with the project in every edition.
1. General workflow
- Draw the wall as usual and open the Wall Properties window.
- Select the “Panel in Cold-Formed Steel” option as the design type.
- Enter the sheathing and stud inputs in the Cold-Formed Steel Panel tab (Section 2) and save with OK.
- For panels on the exterior façade, tick the appropriate edge-axis box in Wall Properties (On Top/Bottom/Left/Right Edge Axis); wind bending is calculated only for these walls (Section 5).
- In Project General Settings, check the design method (LRFD/ASD), the wind velocity pressure and the stud deflection limit (Sections 5 and 6).
- Run the analysis. Panel shear capacity and stud checks are calculated automatically during the analysis; inadequacies appear in the warning list at the end of the analysis (Section 8).
- In the tree on the Report tab of the Report Selection window, tick the “Cold-Formed Steel Member Reports” group and its sub-reports and generate the report (Section 9).
2. Inputs of the “Cold-Formed Steel Panel” tab
| Input | Description | Default |
|---|---|---|
| Left/Top Panel Sheathing Present | Whether there is a sheathing board on the left (top) face of the panel | Present |
| Right/Bottom Panel Sheathing Present | Whether there is a sheathing board on the right (bottom) face of the panel | Present |
| vc,left, vc,right (kN/m) | Characteristic shear strength of the sheathing per unit length (depending on board type, screw diameter and spacing; the note in the tab gives the typical values of TBDY Table 10.5) | 10.2 (11 mm OSB) |
| Stud Profile (C / Sigma) | Cold-formed section to be used for the panel studs; the list is filled from the profile table that comes with the installation | Empty (selected by the user) |
| Stud spacing s (mm) | Centre-to-centre spacing of the intermediate studs | 600 |
| Number of end studs n | Number of studs at each end of the panel; the overturning force is shared among these studs | 2 |
| Stud / track material | Material of the studs, bottom/top tracks and bridging: TS EN 10346 grades or library steel (Section 10) | (default) S350GD |
Older project files that do not contain these inputs open without any change; the fields come with their default values.
3. Panel shear capacity (TBDY 2018)
The shear capacity of the sheathed face(s) is calculated for each cold-formed steel panel:
Vc = 0.6 · vc · L (L: wall length)
- In the range 2 ≤ h/L ≤ 4 the capacity is reduced by the factor 2L/h; if h/L > 4 or L < 0.30 m, the panel does not contribute to the shear capacity.
- If only one face is sheathed, the capacity of that face is used; if both faces are sheathed, the sum is used for equal sheathing, and the rule max(2·smaller, larger) is used for different sheathing.
The result is taken into account as the lateral capacity of the panel in the storey shear distribution and is listed panel by panel in the report.
3.1 Unsheathed panel
If the sheathing ticks on both faces (Left/Top Panel Sheathing Present and Right/Bottom Panel Sheathing Present) are cleared in the Cold-Formed Steel Panel tab, the panel is considered unsheathed:
- The shear capacity of the panel is zero, because the shear capacity comes from the sheathing. The panel is not included in the gypsum-board share calculation either.
- The studs are designed with the unsheathed buckling lengths: Ly = Lz = h, or h/(n+1) with n rows of bridging (Section 4.2).
- If the shear distribution is carried out with the finite element method, the panel practically receives no shear while the stiffness type is Capacity. With the Classical Stiffness type it receives shear in proportion to its stiffness; if this shear exceeds one thousandth of the panel shear of the storey in the same direction, an error is given. In the classical shear distribution the panel receives no shear.
- An information line reporting the unsheathed panels appears in the analysis warnings.
If the panel is actually sheathed, check the face ticks.
3.2 Storey with no panel with shear capacity
If all the panels in one direction (X or Y) on a storey are unsheathed or short (h/L > 4 or L < 0.30 m), no panel remains to carry the lateral load in that direction. In this case the analysis gives the error “kat, X/Y doğrultusu: kesme kapasiteli panel yok” (storey, X/Y direction: no panel with shear capacity) and writes it in the project checklist. Solely so that the storey shear can be distributed, it is assigned to these panels on the assumption that both faces are sheathed; since their capacities remain zero, the panel checks turn out inadequate. Sheathe or lengthen some of the panels. Panels with steel strap cross-bracing are not supported.
4. Stud check (EWM — HCBTİE Chapter 4)
4.1 Demands
For each panel, the analysis extracts the envelope of the wall’s in-plane shear (V) and vertical axial force (N) over all load combinations; the name of the governing combination is shown in the report. The stud demands are derived from this envelope:
| Member | Axial demand | Description |
|---|---|---|
| Intermediate stud | Nint = N · s / L | Share of the vertical load according to tributary width |
| End stud | Nend = max[ N·(s/2)/L + (V·h/L)/n ; Cd ] | Tributary share plus the end force from the overturning moment divided by the number of end studs. Cd is the same distribution calculated combination by combination with the earthquake effect magnified by the overstrength factor D (TBDY 10.4.1.1(a)); the larger one governs. In the report, “(D ile)” (with D) or “(zarf)” (envelope) is written next to the demand. |
4.2 Capacity
For the selected section, the axial compression capacity (Pd) is found with EWM: the smallest of the local buckling (effective widths), distortional buckling and flexural–torsional (global) buckling rows governs. Buckling lengths:
- Strong axis: Lx = panel height h.
- If at least one face is sheathed, Ly = Lz = stud spacing s is taken for the weak axis and torsion, and lateral–torsional buckling is assumed to be restrained; if there is no sheathing, Ly = Lz = h (h/(n+1) if n rows of bridging are defined; see Code Requirements, Anchorage and Foundation in Cold-Formed Steel Buildings).
The gross section properties (A, Ix, Iy) are the manufacturer’s catalogue values in the profile table; the torsion constant, shear centre and warping constant are calculated automatically from the section geometry. In sheathed panels the governing row is mostly distortional buckling; the distortional critical stress is calculated with the general method of HCBTİE 4.10.3.3 or, if selected, with the finite strip method (see Theoretical Basis).
For each panel, the end stud and the intermediate stud are checked as separate rows. Two ratios are calculated, and the larger one is the governing ratio that gives the Adequate / YETERSİZ (inadequate) decision:
- Axial ratio = PEd/Pd (envelope of all load combinations),
- Wind combination ratio = P/Pd + M/Md (only on exterior walls; HCBTİE Eq. 4.8.4).
5. Out-of-plane wind bending and deflection
The studs of walls marked with an edge axis (exterior walls) bend like simple beams under wind pressure perpendicular to the wall face:
- w = max(0.8 · q ; 0.5) kN/m² (0.8: TS 498 pressure coefficient; 0.5 kN/m²: lower limit of the HCBTİE characteristic wind load)
- M = γW · w · b · h² / 8 (b: s for an intermediate stud, s/2 for an end stud; second-order magnification is applied)
q is the “Wind Load” box in the Project General Settings → Load Combinations tab; a value appropriate to the building height according to TS 498 must be entered (0–8 m: 0.5; 8–20 m: 0.8; 20–100 m: 1.1 kN/m²). The snow load in the same tab contributes to the axial force in the wind combination. Wind combinations — LRFD: 1.2G + 1.0Q + 0.5S + 1.6W and 1.2G + 1.6S + 0.8W; ASD: G + 0.75Q + 0.75S + 0.45W and G + 0.6W.
If no cold-formed steel panel in the project is marked as an exterior wall, a line stating this appears in the analysis warning list; wind bending is not skipped silently. A warning is also given if q has not been entered or is lower than the TS 498 value corresponding to the height of the panel’s top level (q is not changed by the program).
Deflection check: In exterior wall studs, the out-of-plane deflection is calculated with the characteristic value of the wind and δ ≤ h/K is checked. The deflection is calculated with the effective moment of inertia at the service moment (HCBTİE 4.9.5); for slender sections it may come out larger than the one calculated with the gross moment of inertia. K is selected from the Stud deflection limit list of the “Cold-Formed Steel Member Design Method” box in the Project General Settings → Code Selection tab (h/120, h/200, h/240 default, h/300, h/360). Since HCBTİE gives no stud-specific limit, the selection should be made by engineering judgement according to the type of finish: h/120 is common for flexible cladding, h/240 for gypsum or OSB sheathing, and h/360 for plaster or ceramic finishes. The result is written in a separate “Sehim” (Deflection) row in the report; if it is exceeded, the stud is considered inadequate.
6. Design method: LRFD / ASD
It is selected from the “Cold-Formed Steel Member Design Method” box in the Project General Settings → Code Selection tab (visible when the building type is cold-formed steel or when the project contains a cold-formed steel panel) and is saved with the project:
| Option | Strength | Load combinations |
|---|---|---|
| LRFD (default) | φc = 0.85, φb = 0.90 (HCBTİE) | The program’s combinations; 1.2G instead of G in combinations containing earthquake; in addition, the HCBTİE 4.3.1 vertical combinations (1.4G; 1.2G + 1.6Q + 0.5S; 1.2G + 1.6S + Q) are generated from the plain G/Q/S results and added to the envelope. |
| ASD | Ωc = 1.80, Ωb = 1.67 (AISI S100) | The program’s combinations are converted to their ASD counterparts; in addition, G + Q, G + S, G + 0.75Q + 0.75S and the G + 0.7E form of the combinations with earthquake are added to the envelope. |
HCBTİE defines only LRFD; the ASD option is for comparison and preliminary sizing. Use LRFD in official calculations. Older projects open with LRFD.
7. Rotational restraint of the sheathing (kφ)
OSB or plywood sheathing restrains the flanges of the stud against rotation and thereby increases the distortional buckling strength (HCBTİE 4.10.3.3, AISI S240). If no data is entered, kφ = 0 is assumed.
- In the “Sheathing rotational restraint to the stud” box of the Wall Properties → Cold-Formed Steel Panel tab, the board type (Undefined / Gypsum board / OSB / Plywood / User kφ), the board bending stiffness (0 = default of the type), the screw spacing and, only for “User kφ”, kφ are entered for the left and right faces. The smaller of the two faces is used in the calculation: if one of the faces is gypsum board, undefined or unsheathed, kφ = 0.
- Conditions: screw spacing ≤ 305 mm and stud spacing ≤ 625 mm; otherwise kφ = 0 is taken and the reason is written in the report.
- In the stud note of the report, the kφ value of each face, or the reason for zero, and the value used are written.
8. Analysis warnings
| Warning | Meaning / action |
|---|---|
| “… hafif çelik panel dikme hesabı yapılamadı: Dikme profili seçilmedi” (… cold-formed steel panel stud calculation could not be performed: Stud profile not selected) | No stud profile has been selected in the panel’s tab. Select a profile in the Wall Properties → Cold-Formed Steel Panel tab. |
| “… hafif çelik panel KENAR/ARA dikmesi yetersiz (oran=…)” (… cold-formed steel panel END/INTERMEDIATE stud inadequate (ratio=…)) | The governing ratio of the stud concerned exceeds 1. Select a larger or thicker profile, reduce the stud spacing, or increase the number of end studs. |
| “Hafif çelik panellerde bina kenar aksı (dış duvar) işaretli duvar yok …” (There is no wall marked with a building edge axis (exterior wall) among the cold-formed steel panels …) | Wind bending was not calculated because no panel is marked as an exterior wall. For façade panels, tick the edge-axis boxes. |
| “… hafif çelik panel dikme sehimi fazla (rüzgâr: sehim=… mm > h/K=… mm)” (… cold-formed steel panel stud deflection excessive (wind: deflection=… mm > h/K=… mm)) | The out-of-plane deflection of the exterior wall stud exceeds the selected limit. Select a stiffer profile, reduce the stud spacing, or review the limit if appropriate for the type of sheathing. |
| “Rüzgâr basıncı q girilmemiş …” / “… TS 498 yükseklik kademesinin altında …” (Wind pressure q has not been entered … / … below the TS 498 height step …) | Enter the Project General Settings → Load Combinations → Wind Load value appropriate to the building height. |
| Unsheathed panel information line | Panels marked unsheathed on both faces are listed; these panels carry no shear (Section 3.1). If the panel is sheathed, correct the face ticks. |
| “… kaplamasız … katılamaz ancak analizde V=…” (… unsheathed … cannot participate, but in the analysis V=…) | With the Classical Stiffness type, an unsheathed panel received more than one thousandth of the panel shear of the storey in the analysis. Sheathe the panel or use the Capacity type. |
| “kat, X/Y doğrultusu: kesme kapasiteli panel yok” (storey, X/Y direction: no panel with shear capacity) | There is no panel able to carry lateral load in that direction (Section 3.2). Sheathe or lengthen some of the panels. |
9. Reports
In the tree on the Report Selection → Report tab there is the “Cold-Formed Steel Member Reports” group (visible if the project contains a cold-formed steel panel):
- Cold-Formed Steel Panel Design: Panel by panel, the sheathing information, h, L, vc inputs and the sheathing shear capacities.
- Cold-Formed Steel Stud Design (EWM): Storey by storey, panel by panel — panel name and profile, geometry (h, L, s, n), design method and wind pressure, envelope forces (with the name of the governing combination), demand, capacity, axial ratio, governing ratio and status for the end and intermediate studs; for exterior walls the wind combination row and deflection; anchorage and panel shear rows; bottom and top track and bridging rows (demand, tension and compression strength, ratio, collector, bridging force and HCBTİE 6 detail warnings); a note on calculation assumptions.
- Cold-Formed Steel Beam Design (EWM) and Cold-Formed Steel Column Design (EWM): If the project contains such members (see Cold-Formed Steel Beam and Column Design).
Reports are produced in Turkish or English according to the program language setting; after the analysis is completed they are obtained with “Generate All Selected Reports” and can be exported as PDF/DOCX.
10. Panel material
- In the Stud / track material box on the Wall Properties → Light Steel Panel tab, the first row is “(default) S350GD”; it is followed by the TS EN 10346 grades (S220GD … S450GD) and the steels in the material library. The Fy/Fu values are written next to the selection; “(?)” means an unrecognised name, and “!TBDY 10.2.3.2” means a material that does not satisfy that requirement. In multiple selection the box stays empty for walls with different materials; if it is not changed, the materials of the walls are preserved.
- The material is used in the stud, bottom/top track and bridging checks, in the screw and anchor connections, and in the slab–panel connection.
- If Fy < 235 MPa (e.g. S220GD) or Fu/Fy < 1.08, the analysis gives an error and a project checklist line. A summary of the materials used appears in the analysis warnings as an information line.
- The selection is saved in the project file. Old projects open with the default S350GD; their results do not change.
11. Panel studs in the wall plan
- In the Drawing Selection → wall plan sheet, studs are drawn inside light steel panel walls: the C symbol is the stud section (web in the direction of the wall thickness, flanges at the sheathing faces, dimensions from the catalogue profile; the web does not exceed the wall thickness).
- At each wall end, n end studs are drawn side by side (the number of end studs in Wall Properties), and intermediate studs are drawn at spacing s from the drawing start of the wall. At an end connected to another wall (corner, T) the end group starts from the inner face of the joining wall; the corner square is left to the joining wall. Because the program splits the wall at door and window openings, there are also wall-end end studs at the edges of openings.
- Filled circle: hold-down at each end, on the inner side of the end group. Triangles: shear anchors; the number is taken from the last analysis (the required number if none was entered) or from the entered number/spacing, arranged at equal spacing along the wall; “n x bolt/screw Ø” is written beside them.
- A label in the middle of the wall: profile s=… n=… material. Studs and anchors found inadequate in the last analysis are on the HafifCelikYetersiz (red) layer; the others are on the HafifCelikDikme (blue) and HafifCelikBaglanti (magenta) layers.
- The stud layout is a drawing assumption: the analysis designs the studs with spacing and number of end studs, and does not separately model the joint and corner studs. The responsible engineer determines the construction detail (corner and T joint studs, opening lintel).
- In a braced panel, a green brace line is drawn 1 cm outside the stud flange on the braced face (on both faces for double-face bracing), an X symbol across the wall thickness in the middle of each bay, and the brace label at the upper side of the wall, above the stud and shear anchor labels; there is an explanation line at the bottom of the sheet. The brace, gusset plate and end pattern are drawn in the axis elevation (Section 12).
12. Panel wall in axis elevations
- Drawing Selection → Elevations → Draw Section / Side View (axis elevations) shows light steel panel walls with their framing: bottom track (at the base level) and top track (below wall top level − the height of the bond beam above the wall; two strips for a double top track) strips, studs (same positions as in the plan), and bridging rows (dividing the free stud length equally).
- At the ends, a hold-down strip on the inner side of the end stud group; shear anchors going from the bottom track down to the base (number from the last analysis or from the entered value). Below the top track there is a stud spacing dimension chain (spacings shorter than 15 cm are not written).
- In the middle of the wall, below the wall name: stud profile / s / n / material; the bottom and top track profiles (including those automatically selected in the last analysis); the hold-down, shear anchor and bridging row counts. Tracks, bridging, studs and anchors found inadequate in the last analysis are on the red layer.
- The opening lintel is not drawn: the program splits the wall at the opening, and the beam above the opening is drawn separately as a bond beam/beam.
- In a braced panel, two braces are drawn in each bay from the panel corner to the opposite corner (a band of the strap width; the web height for a profile). If there is a gusset plate, a right-triangle plate at the four corners, an nr × nc screw or bolt pattern (p1, p2, e1) at the brace ends, and the screws connecting the plate to the chord stud (at the stud flange) and to the track are shown. Two lines of text are written in the middle of the wall: the brace (number of faces, strap b×t or profile, material, number of bays, end reinforcement) and the end connection (pattern, plate thickness or “no plate”, number of plate screws). The text is placed in the upper triangle between the two braces, away from the crossing of the X, below the dimension chain; if the hold-down strip overlaps the gusset plate, the part left behind the plate is drawn with a dashed line.
- The brace is on the HafifCelikCapraz (green) layer, the plate and screws on the HafifCelikBaglanti (magenta) layer. If, in the last analysis, the brace force, the net section or a link of the connection is inadequate, or the connection is weaker than the brace, the relevant part is drawn on the red layer. The pattern and plate dimensions are a drawing assumption; the responsible engineer determines the construction detail.
13. Braced panel
- The Wall Properties → Light Steel Brace tab (Ultimate; next to the Track tab) lets you select the panel system: Sheathed (TBDY 10.3) or Braced (TBDY 10.4.2). When Braced is selected, the shear capacity of the wall is calculated from the braces only; the sheathing only restrains the studs.
- The brace type is a strap (tension only; width b and thickness t) or a profile (tension and compression; C / C+ / U from the catalogue). If the material is left blank, the stud material is used. The number of braced faces is 1 or 2; the number of bays is the number of X patterns along the wall. If profile braces are connected at the X crossing, the buckling length is taken as Ld/2.
- The brace angle and length are calculated from the bay width (L / number of bays) and the stud length. The stud length is found by subtracting the height of the bond beam above the wall from the storey height, and is the same as the frame height drawn in the axis elevation.
- Light Steel Brace Connection tab: screw diameter and number of screws or bolts per brace end (0 = no check), number of holes in the first row of the net section, gusset plate thickness (0 = stud thickness).
- Details of the same tab: connection type (screw or bolt; bolt diameter and grade), pattern (rows nr × columns nc, p1, p2, e1, e2; if left blank, the default pattern from the number of screws), gusset plate (Automatic / Yes / No; if none, the strap is connected directly to the stud and track), plate material, end distance in the plate, free compression length of the plate for a profile brace, numbers of screws connecting the plate to the chord stud and to the track, and strap end reinforcement (width and total thickness in the connection zone; for example 2×t for a double-layer strap). The reinforcement improves the net section condition (Eq. 10.23) and block shear rupture.
- Connection checks: spacing and edge distances (greater than 3d and 1.5d), block shear rupture at the brace end and effective net section in the profile (nominal capacity ≥ 1.20·AgFy: the end must not rupture before the brace yields), fastener group, gusset plate (Whitmore yielding and rupture, block shear rupture, compression) and plate screws, with the brace force magnified by D. If any connection element is weaker than the brace, a “not ductile” error is given. In a screwed thin strap, block shear rupture is often governing: few columns, many rows and a large e1 increase the capacity.
- In the analysis, the brace tension and compression, the net section (AnetFu ≥ 1.20·AgFy), the connection (with D), the moment T·e on the chord stud for a strap on one face, the blocking (at least one row; Track tab) and the limited ductility of the building are checked. The results are in the panel shear row of the wall in the report.
- In S350GD, Fu/Fy = 1.20, so a braced member with holes does not satisfy the net section condition: select S250GD or S280GD, or use a connection without holes (welded).
- Finite element model: if the panel stiffness type is Classical and the walls are modelled with bar elements, the braces enter the model as explicit diagonal bars (the lateral load of the wall is carried by the braces; the wall forces are the sum of the bar and brace forces). In the Capacity type and in the shell wall model, the panel is modelled with an equivalent stiffness.
- For the calculation basis see Theoretical Basis of Light Steel Design, for verification see Light Steel Verification Studies, and for a step-by-step example see Worked Example: Braced Light Steel Panel.
14. Frequently asked questions
The panel shear capacity is shown as 0. h/L may be > 4 or L < 0.30 m, or sheathing may not be ticked on either face (unsheathed panel, Section 3.1). In older projects the sheathing strength may come with the old default (2.7 kN/m); check it in the tab.
The stud profile list is empty or shows only Sigma profiles. The profiles are loaded from the HafifCelikProfil.txt file (527 profiles) in the installation folder. If this file cannot be found, the backup HafifCelikSigma.txt (90 Sigma profiles) is used; if neither exists, the list stays empty. Reinstall the update.
The stud profile comes up empty in a new cold-formed steel wall. The profile is selected by the user: Wall Properties → Cold-Formed Steel Panel → Stud Profile. If it is not selected, the analysis gives a warning.
There is no wind combination row in the report; it says “iç duvar” (interior wall). The wall has not been marked with any of the edge-axis boxes. If it is a façade wall, tick the relevant edge axis in Wall Properties and repeat the analysis.
“(D ile)” (with D) is written next to the end stud demand. According to TBDY 10.4.1.1(a), the end stud demand is also calculated from the earthquake combinations magnified by the overstrength factor D; in a multi-storey building the overturning moment accumulated from the upper storeys is also taken into account. If the ratio is inadequate, increase the number of end studs or the profile.
There is a note “Kenar rijitleştirici (HCBTİE 4.9.3)” (Edge stiffener (HCBTİE 4.9.3)) in the report footnote. The lip is not sufficient to fully stiffen the flange; the flange plate buckling coefficient and the effective widths have been reduced according to the code. If a profile with a thicker wall or a longer lip is selected, the reduction becomes smaller.
Why is the governing row always distortional buckling in a sheathed panel? The sheathing limits weak-axis and torsional buckling to the stud spacing; in thin-walled sections the lowest strength in this case is usually given by distortional buckling. Entering the rotational restraint of the sheathing (Section 7) and the finite strip option (for Sigma sections) calculate this strength more realistically.